Chapter 2 - AsconBasicIOLib
77
Input tables
The configuration of the module inputs is done using the following strings. For
example, if the value “MV0100” is assigned to the signal "Ch1Type", this means
that the input channel 1 is configured as 0...100mV input.
The following table gives in detail the Range for each input that may be connected
to the module.
String Sensor
TCJ (default value) Thermocouple J
TCK Thermocouple K
TCL Thermocouple L
TCN Thermocouple N
TCR Thermocouple R
TCS Thermocouple S
TCT Thermocouple T
MV0100 Linear Input 0... 100 mV
MV01000 Linear Input 0... 1000 mV
MVPM100 Linear Input ±100 mV
MVPM1000 Linear Input ±1000 mV
String Range Lo Range Hi
TCJ -210°C (-346°F) 1200°C (2192°F)
TCK -200°C (-328°F) 1372°C (2501.6°F)
TCL -200°C (-328°F) 600°C (1112°F)
TCN 0°C (32°F) 1300°C (2372°F)
TCR 0°C (32°F) 1600°C (2912°F)
TCS 0°C (32°F) 1760°C (3200°F)
TCT -200°C (-328°F) 400°C (752°F)
PT100 -200°C (-328°F) 600°C (1112°F)
PT1000 -200°C (-328°F) 600°C (1112°F)
MV0100 0V 100mV
MV01000 0V 1V
MVPM100 -100mV 100mV
MVPM1000 -1V 1V